Experimental Investigation on an Intermittent Ammonia Absorption Refrigeration System

Show simple item record

dc.contributor.advisor Islam, Prof. Dr. Mohammad Ariful
dc.contributor.author Mondal, Dipayan
dc.date.accessioned 2018-08-29T03:50:29Z
dc.date.available 2018-08-29T03:50:29Z
dc.date.copyright 2014
dc.date.issued 2014-09
dc.identifier.other ID 1205554
dc.identifier.uri http://hdl.handle.net/20.500.12228/419
dc.description This thesis is submitted to the Department of Mechanical Engineering, Khulna University of Engineering & Technology in partial fulfillment of the requirements for the degree of Master of Science in Mechanical Engineering, Septmber 2014. en_US
dc.description Cataloged from PDF Version of Thesis.
dc.description Includes bibliographical references (pages 91-94).
dc.description.abstract This project work describes the experimental investigation on an intermittent ammonia absorption refrigeration system which consists of a generator/ absorber, a condenser, an evaporator and an expansion valve. The system used 2.5 kg of ammonia as refrigerant and 1.5 kg of calcium chloride as absorbent initially in generator and this NH3-CaCl2 refrigerant-absorbent pair is widely used to intermittent refrigeration system. There are two modes where in desorption mode, an oil bath arrangement heat source provides heat to the generator and the generator drives of the vapor form refrigerant around the system through a condenser to evaporator. The evaporator pipes were placed outside to the evaporator container which was insulated and 3 kg of water was filled to be the load for cooling into the evaporator container. During the absorption mode, the liquid refrigerant absorbed heat from the surrounding water and performed cooling. The average refrigeration temperature was found to be 13.250C with a minimum value of 11.50C for a period of time up to 2.5 hours absorption. The coefficient of performance was obtained on the average of 0.154 with a maximum value of 0.192. This coefficient of performance was higher than the coefficients of performance found by Vanek [1], atejanekarn [2] and Moreno -Q uintanar [3] on their intermittent solar absorption system and also lower than the COP found by Tangka [4] developed intermittent solar absorption system. The generator temperature was found to be 91 .400C corresponding to the oil bath temperature up to 1100C during 2.5 hours desorption and the pressure was to be found 10.5 bar. On an average the system could provide the heat gained by the generator of 1492.96 kJ and the refrigeration effect of 223.65 kJ. en_US
dc.description.statementofresponsibility Dipayan Mondal
dc.format.extent 94 pages
dc.language.iso en_US en_US
dc.publisher Khulna University of Engineering & Technology (KUET), Khulna, Bangladesh. en_US
dc.rights Khulna University of Engineering & Technology (KUET) thesis/dissertation/internship reports are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission.
dc.subject Ammonia Absorption en_US
dc.subject Refrigeration System en_US
dc.subject Vapor Absorption en_US
dc.title Experimental Investigation on an Intermittent Ammonia Absorption Refrigeration System en_US